Range | TeSys |
---|---|
Range of product | TeSys F |
Product or component type | Contactor |
Device short name | LC1F |
Contactor application | Resistive load Motor control |
Utilisation category | AC-3 AC-1 AC-4 |
Poles description | 3P |
[Ue] rated operational voltage | <= 1000 V AC 50/60 Hz <= 460 V DC |
[Uc] control circuit voltage | 220 V AC 40...400 Hz |
[Ie] rated operational current | 1600 A (at <40 °C) at <= 440 V AC AC-1 780 A (at <55 °C) at <= 440 V AC AC-3 |
[Uimp] rated impulse withstand voltage | 8 kV |
---|---|
[Ith] conventional free air thermal current | 1600 A (at 40 °C) |
Rated breaking capacity | 6240 A conforming to IEC 60947-4-1 |
[Icw] rated short-time withstand current | 3000 A 40 °C - 3 min 6250 A 40 °C - 10 s 5600 A 40 °C - 30 s 4600 A 40 °C - 1 min 2200 A 40 °C - 10 min |
Associated fuse rating | 1600 A gG at <= 440 V 800 A aM at <= 440 V |
Average impedance | 0.1 mOhm - Ith 1600 A 50 Hz |
[Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C |
Power dissipation per pole | 250 W AC-1 60 W AC-3 |
Overvoltage category | III |
power pole contact composition | 3 NO |
Motor power kW | 450 kW at 1000 V AC 50/60 Hz (AC-3) 400 kW at 380...400 V AC 50/60 Hz (AC-3) 425 kW at 415 V AC 50/60 Hz (AC-3) 425 kW at 440 V AC 50/60 Hz (AC-3) 450 kW at 500 V AC 50/60 Hz (AC-3) 475 kW at 660...690 V AC 50/60 Hz (AC-3) 220 kW at 220...230 V AC 50/60 Hz (AC-3) 110 kW at 400 V AC 50/60 Hz (AC-4) |
Control circuit voltage limits | Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.2...0.4 Uc 40...400 Hz (at 55 °C) |
Mechanical durability | 5 Mcycles |
Inrush power in VA | 2100 VA, 40...400 Hz cos phi 0.9 (at 20 °C) |
Hold-in power consumption in VA | 50 VA, 40...400 Hz cos phi 0.9 (at 20 °C) |
Maximum operating rate | 600 cyc/h 55 °C |
Operating time | 40...80 ms closing 130...230 ms opening |
Connections - terminals | Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 100 x 5 mm Power circuit: bolted connection |
Tightening torque | Control circuit: 1.2 N.m Power circuit: 58 N.m |
Mounting support | Plate |
Heat dissipation | 44 W |
motor power range | 250…500 kW at 380…440 V 3 phases 110…220 kW at 200…240 V 3 phases 250…500 kW at 480…500 V 3 phases |
Motor starter type | Direct on-line contactor |
Contactor coil voltage | 220 V AC standard |
Standards | EN 60947-4-1 IEC 60947-1 EN 60947-1 JIS C8201-4-1 IEC 60947-4-1 |
Product certifications | DNV RMRoS LROS (Lloyds register of shipping) CSA CB UL RINA ABS BV |
Compatibility code | LC1F |
Control circuit type | AC at 40...400 Hz |
IP degree of protection | IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106 |
---|---|
Protective treatment | TH |
Ambient air temperature for operation | -5…55 °C |
Ambient air temperature for storage | -60…80 °C |
Permissible ambient air temperature around the device | -40…70 °C |
Height | 434 mm |
Width | 702 mm |
Depth | 255 mm |
Operating altitude | 3000 m without derating |
Net weight | 39.5 kg |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 44.0 cm |
Package 1 Width | 41.0 cm |
Package 1 Length | 95.0 cm |
Package 1 Weight | 47.59 kg |
Unit Type of Package 2 | PAL |
Number of Units in Package 2 | 2 |
Package 2 Height | 195.0 cm |
Package 2 Width | 120.0 cm |
Package 2 Length | 80.0 cm |
Package 2 Weight | 122.2 kg |