Master range | Easy Series |
---|---|
Range of product | EasyPact |
Product name | EasyPact EXE |
Product or component type | Circuit breaker |
Switching device | Circuit breaker |
Breaking technology | Vacuum |
Pole type | Open |
Number of poles | 3 |
Network type | AC |
Type of installation | Indoor |
variant | Basic version |
Standards | IEC 62271-100:2012 |
Rated voltage (Ur) | 12 kV |
Rated short-duration power frequency withstand voltage (Ud) / Common value | 28 kV |
Rated lightning impulse withstand voltage (Up) / Common value | 75 kV |
Rated frequency (fr) | 50/60 Hz |
Rated current [Ik] | 1250 A |
Short-circuit current | 25 kA |
Rated short-circuit making current | 62.5 kA 50 Hz 65 kA 60 Hz |
DC time constant (τ) | 45 ms |
Rated short-time withstand current (Ik) | 20 kA |
Rated duration of short-circuit (tk) | 3 s |
Rated peak withstand current (Ip) | 62.5 kA 50 Hz 65 kA 60 Hz |
Rated first pole-to-clear factor (kpp) | 1.5 |
Rated out-of-phase breaking current (Id) | 7.88 kA |
Rated line-charging breaking current (Ii) | 10 A |
Rated cable-charging breaking current (Ic) | 25 A |
rated single capacitor bank-breaking current (Isb) | 400 A |
Rated operating sequence | O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO |
Auxiliary contact composition | 4 NO + 4 NC |
---|---|
Operating time | < 50 ms opening < 66 ms breaking < 71 ms closing |
Classification for electrical endurance | E2 |
Number of operations at short-circuit breaking current | 50 |
Classification for the connection to the network | S1 |
Classification for capacitive currents | C2 |
Width | 477 mm |
Depth | 429 mm |
Phase distance | 150 mm |
Clearance in air to earth | 175 mm |
Upper lower connection distance | 270 mm |